At rated load, ventilation must keep the EPS room within the maker's maximum ambient, counting all heat from the engine and exhaust; combustion air is supplied; for Level 1, supply and discharge air come from and go to outdoors by exterior openings or 2-hour rated transfer systems with no fire dampers or self-closing devices in those openings; radiator air discharge is ducted outdoors within the allowed static restriction; motor-operated dampers spring open; Level 1 rooms stay at 4.5 C (40 F) or above; and design allows for heat, cold, dust, humidity, snow, louvers and wind.