The EPS room is not used for unrelated purposes (maintenance parts, tools and manuals may be stored); carbon dioxide or halon suppression is not used unless combustion air comes from outside, and automatic dry chemical only with the maker's certification of no harm; fire detection follows NFPA 72; outdoor and rooftop Level 1 sets are protected against lightning; and in seismic areas the EPS and its distribution, fuel and water lines are designed to limit earthquake damage and keep working during and after the event.