Heating and cooling keep the equipment within the maker's ambient range both with normal power and during the emergency; flammable gas from batteries or other electrochemical storage is diffused and vented to keep concentrations within NFPA 855 or other applicable codes; vented battery rooms have openings or airflow placed to stop gas pockets forming per NFPA 1; and circulating or exhaust fans use motors suited to the duty.