NFPA 110-2025 Standard for Emergency and Standby Power Systems
Chapter 7: Installation and environmental considerations – NFPA 110-2025 Standard for Emergency and Standby Power Systems

NFPA 110-2025 Standard for Emergency and Standby Power Systems 7.3: 7.3 Lighting at the EPS location

Level 1 and Level 2 EPS locations need battery-powered emergency lighting (not for outdoor units without walk-in access), the lighting charger and normal room lighting take supply downstream of the transfer switch, and a Level 1 room is lit to 32.3 lux (3 footcandles) unless another accepted requirement applies.