EPSS distribution and wiring follow NFPA 70, and in health care NFPA 99 as well; conductors from the EPS terminals to the first overcurrent device are kept short; flexible conduit sections isolate vibration at the transfer switch, control and accessory connections, with stranded wire and bushings; ac support equipment needed to run the EPS is fed from the ATS load side or the EPS output ahead of its main protection; and starting batteries sit next to the starter with cables sized to limit voltage drop and charger leads permanently connected.