Internal substations and switchrooms should have maintained lighting averaging 200 lux, escape lighting of 15 lux for 3 h supported by a secondary source, temperature kept above 10 C and within equipment limits, humidity controlled (it promotes partial discharge) and transformer heat removed, naturally where possible. As a minimum they should hold safety posters (including first aid and electric shock treatment), current single-line diagrams and, at the intake substation, a mimic board, a key cabinet with the site logbook, a sign identifying the LV earthing system (also at each final distribution board and MCC), a battery charger for trip circuits with on-load test facility, storage for tools and test equipment and fixed lifting equipment.