NFPA 110-2025 Standard for Emergency and Standby Power Systems
Chapter 7: Installation and environmental considerations – NFPA 110-2025 Standard for Emergency and Standby Power Systems

NFPA 110-2025 Standard for Emergency and Standby Power Systems 7.10: 7.10 Exhaust system

Exhaust equipment follows NFPA 37 and is gastight, terminating where fumes cannot re-enter buildings or air intakes; piping connects through a flexible connector and is independently supported, with condensate traps and drains, allowance for expansion, mufflers close to the engine, thimbles through combustible walls, a weather-proof termination, heat clearance from conduit, fuel piping and luminaires, insulation inside buildings, and sizing that avoids excessive back pressure.