AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 3: Additional requirements for permanently connected generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 3.2-environment: 3.2 Location: ventilation and lighting of generator rooms

A room or enclosure with a permanently connected set must be ventilated so running the set raises the room temperature by no more than 10 C and toxic or explosive fumes cannot build up to dangerous levels (AS 1668.2), and must have lighting adequate for safe and effective operation of equipment and controls.