For Level 1 the EPS sits in a separate room with a 2-hour fire rating, or in an outdoor enclosure that resists snow and rain, with no unrelated equipment in the room; Level 1 EPSS equipment may not share a room with normal service equipment over 150 V to ground and 1000 A or more. EPSS rooms are placed and designed to limit flooding damage (including firefighting water and sewer backup) and supply interruption, the EPS keeps 0.9 m (36 in.) of access around the skid in the access direction (outdoor housings excepted), and failure of one converter should not stop others.