NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems
Chapter 7: Installation and environmental considerations – NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems

NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems 7.2: 7.2 Location

The SEPSS sits in rooms meeting the maker's environmental specification and NFPA 855 where it applies; equipment serving Level 1 loads may not share a room with normal supply equipment over 150 V to ground and rated 1000 A or more; rooms are placed to limit flooding damage including firefighting water and sewer backup; working clearance follows NFPA 70 Table 110.26(A)(1); and a unit emergency light is provided at the SEPSS if none exists.