NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition) 8.1-8.20: HV substation and LV switchroom location and construction

Substations and switchrooms should be assessed for environmental risks (flooding, drainage overflow, ventilation), not sited under bulk water or wet services, located per HTM 05-02 fire adjacencies, built from fire-resisting materials to Approved Document B, robust enough to contain an internal electrical explosion (external units with pressure relief), protected against water ingress, bunded where fluid-filled transformers are used, and finished to limit dust. Outward-opening doors should be large enough to replace equipment. External equipment should be kept clear of live vegetation by at least 3 m.