AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.2: 2.2 Location of generating sets: exhaust, weather, hazardous areas and fuel fire risk

A set must not be operated anywhere its exhaust, smoke or fumes might build up to dangerous levels, or find their way, directly or indirectly, into enclosed spaces people occupy. Sets must not be installed in damp or weather-exposed places unless suitably protected, in hazardous areas unless equipment and installation meet AS/NZS 3000, the AS/NZS 60079 series and any regulator's requirements, or where the location would put the set's fuel tanks and fittings at fire risk. In New Zealand tunnelling, reduced low voltage diesel sets with exhaust conditioning or suitable ventilation may be used (moved to the end of the clause by A1).

Maintained by Gerard Blokdyk

What else in your programme already covers this

This control maps to 2 controls across 1 other frameworks. If you already hold one of them, the evidence you collected for it is the starting point here rather than new work.

  • 7.10 7.10 Exhaust system
  • 7.2 7.2 Location

Every mapping shown was judged rather than inferred from wording similarity, and the ones that failed review are published too. See the coverage reports and what was rejected.