Tanks are sized for the class and installed and maintained to NFPA 30, 37, 54 and 58; the fuel system delivers clean fuel and tanks are sized so fuel is used within its storage life, or stale or contaminated fuel is remediated or replaced. Tanks are close enough for the engine fuel pump lift or use a transfer pump and day tank; piping is compatible metal (no galvanized), vents and fills keep water out, flexible approved fuel lines connect the engine, day tanks and returns are arranged to drain freely, integral tank volumes indoors or on roofs are limited, gas supplies tap ahead of the building's main shutoff and are labelled, manual fuel valves are the indicating type, and automatically actuated valves that could cut fuel at a critical time are not installed.