NFPA 110-2025 Standard for Emergency and Standby Power Systems 5.6.4.6-5.6.4.7: 5.6.4.6 and 5.6.4.7 Automatic battery chargers

Besides any engine-driven charger, an automatic charger maintains the starting and control batteries. Without manual switching it must charge a fully discharged battery without damage, restore it to full ampere-hour capacity within 24 hours (Level 1) or 36 hours (Level 2), carry dc ammeter and voltmeter within 5 percent, be permanently marked with battery capacity range, output and battery data for replacements, match the batteries supplied and, at Level 1, compensate charge rate for temperature; low battery voltage alarm contacts are required.