An engine-driven set that the AHJ has approved, sized to 700.4, starts automatically on normal power failure, transfers and runs the emergency circuits, and has a delay against retransfer on short restorations; batteries used for control, signals or starting have a charger independent of the set, and chargers and ventilation dampers needed to run the set are on the emergency system; sets slower than 10 seconds are allowed with an auxiliary supply that bridges until they take load; an outdoor set's readily accessible disconnect within sight may serve as the building disconnect.