AS/NZS 3010:2017 Electrical Installations Generating Sets
Section 2: General requirements for the installation of generating sets – AS/NZS 3010:2017 Electrical Installations Generating Sets

AS/NZS 3010:2017 Electrical Installations Generating Sets 2.4.4: 2.4.4 Starting batteries and battery charging

Prime mover batteries must suit continuous float charging and the starter motor current. They are charged by the set's own charging generator while running and/or by a battery charger from a power supply whether the set is running or stopped; flooded or valve regulated lead-acid types suited to float charging are examples, emergency supply systems may have extra battery requirements in other standards, and AS 2676 and AS 3011 cover battery installation and maintenance.