An ATS must operate electrically and hold mechanically, transfer and retransfer automatically, and show not-in-automatic visibly. Undervoltage sensing on every ungrounded phase of the primary source starts the EPS and transfer when any phase falls below load minimums and retransfers when all phases are back within limits for a set time; voltage and frequency sensing on the EPS inhibits transfer until both are acceptable (the sensing may sit in the engine panel). Mechanical interlocking or an approved alternative prevents paralleling the sources, and instructions and equipment allow safe manual nonelectric transfer if the switch fails.