NFPA 110-2025 Standard for Emergency and Standby Power Systems
Chapter 5: Emergency power supply: energy sources, converters and accessories – NFPA 110-2025 Standard for Emergency and Standby Power Systems

NFPA 110-2025 Standard for Emergency and Standby Power Systems 5.6.6: 5.6.6 Remote controls, alarms and annunciation

A remote common audible alarm is required, powered by the starting battery or, if impracticable, another EPS-supplied source. Level 1 needs local annunciation plus facility or network remote annunciation; Level 2 needs local annunciation. Alarm silencing must re-arm so a new or recurring fault sounds again, or a manual silence that never blocks later alarms is used.