NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems
Chapter 5: Energy sources, converters, inverters and accessories – NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems

NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems 5.3.3: 5.3.3 Annunciation

A Level 1 SEPSS needs local annunciation plus annunciation elsewhere on site or off site through a network; a Level 2 SEPSS needs local annunciation. Local means on the equipment or in its room, facility remote means on site outside that room, network remote means off site.