NFPA 70 National Electrical Code 2023 Article 701 Legally Required Standby Systems
Part I: General – NFPA 70 National Electrical Code 2023 Article 701 Legally Required Standby Systems

NFPA 70 National Electrical Code 2023 Article 701 Legally Required Standby Systems 701.6: 701.6 Signals

Audible and visual signals are provided where practicable to show a malfunction of the standby source, that it is carrying load, a charging fault on a battery needed for source readiness including engine starting, and a ground fault on a solidly grounded wye standby system above 150 V to ground with devices of 1000 A or more, sensed at or ahead of the source's main disconnect with a maximum setting of 1200 A and response instructions posted at the sensor; paralleled sources may sense elsewhere.