Sets should be specified to BS 7698 or ISO 8528, engines to BS ISO 3046 and alternators to BS EN 60034, with attention to the engine governor and alternator voltage regulation. Engines should be prime-rated (Class A): able to run at rated load for 12 consecutive hours including a 10% overload for up to 1 hour, with maintenance done. Load acceptance categories range from 100% to 25%; a high initial acceptance factor is the aim, and Category 2 (80%) of Class A is likely to suit most healthcare premises, balanced against cost and synchronising time. Larger engines should be turbocharged.