NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)
Chapter 11: Tertiary power supplies (batteries, UPS, inverters) – NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)

NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition) 11.19-11.21: Generator starting battery capacity and charging

Generator batteries should be sized so that, when 25% discharged at 0 C, they can make three successive 10-second starting attempts 3 seconds apart, and should be able to crank the engine continuously for 60 seconds at 0 C. The stationary charger and the belt-driven alternator should both charge at the correct float voltage, and the battery should give a breakaway voltage acceptable to the engine maker.