Tertiary supplies are backup for a limited autonomy or to start secondary supplies, not long-term sources. VRLA batteries (BS EN 60896-21 and -22, threaded insert posts, flame-retardant cases) are usual for UPS; their life falls sharply above about 20 C (about half at 30 C, a quarter at 40 C) and overheating creates fire risk, so battery locations need suitable ventilation or cooling. In practice VRLA batteries are replaced at about 80% of design life. Chargers should meet standards and the battery maker's requirements, and remote temperature alarms in battery locations should be considered.