Starting is by an electric starter (positive-shift solenoid, cranking without overheating at the maker's speed at the lowest expected ambient) or by another stored-energy system (not pyrotechnic) approved by the AHJ that gives two full cranking periods, automatic recharge from the emergency source and black start. Diesel and spark-ignited engines follow Table 5.6.4.2: cycle cranking of about 15 seconds on, 15 seconds off within a 75 second limit, or continuous cranking within 45 seconds (allowed for diesels and small spark-ignited sets), with two independent crank termination means.