Tripping and closing battery units should suit the protection and control system, be sized with the switchgear maker for all switching and protection operations, include facilities to test charge, terminal voltage and condition, and be fully rated with overload capacity to carry the full burden for 8 hours. Dual rectifier and dual battery systems should be considered, dual rectifiers at minimum, with rectifier alarms relayed to the BMS.