Within every period of 36 months a Level 1 EPSS runs continuously for the duration of its class, which may stop after 4 continuous hours for longer classes. The test starts by operating at least one ATS test function and then all others, or by opening the normal supply to every ATS in the EPSS; other loads need not lose power. Minimum load is 30 percent of nameplate kW for diesels (load bank allowed) or the exhaust temperature load the maker recommends, and the available EPSS load for spark-ignited sets. It may be combined with a monthly test and the annual load bank test, in which case the last hour is at 75 percent or more of nameplate kW.