Diesel sets that cannot meet the monthly loading rule are exercised monthly on the available EPSS load and, once a year, on supplemental load of at least 50 percent of nameplate kW for 30 continuous minutes and then at least 75 percent for one continuous hour, 1.5 continuous hours in all.
This control maps to 3 controls across 2 other frameworks. If you already hold one of them, the evidence you collected for it is the starting point here rather than new work.
Every mapping shown was judged rather than inferred from wording similarity, and the ones that failed review are published too. See the coverage reports and what was rejected.
The graph holds this control, the 3 it maps to, and the evidence behind each claim, over MCP and REST.