NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems 8.4.4: 8.4.4 Annual load test

Once a year the SEPSS is load tested either at its full rated load for 60 percent of its class duration or at 60 percent of rated load for the whole class duration.