Long-term paralleling with the PES under G59/3-2 minimises disruption. Without it, testing on building load needs a short supply interruption which may be unacceptable, so tests should then use a load bank with reactive and resistive components; purely resistive load banks may damage cylinders and liners through carbon build-up.