Generators at different points in the network should be arranged as parallel-operated sets with collective redundancy, and where areas are grade B or above, multiple sets with built-in redundancy should be used. The total time to supply (detection plus run-up under 15 s) should include synchronising enough sets to exceed the load to be supported. All sets should start on mains failure; after stabilising (normally under 5 minutes) the number on line may be adjusted. If sets are switched in and out with load, the disconnect thresholds should be defined carefully and reviewed regularly, weighing light-load running against excess capacity.