Maintenance should include weekly visual inspection of primary and secondary supplies (coolant and lubricant leaks, battery charging, ventilation, instruments), and functional tests at most every three months including on-load battery cell voltage and charging current per the battery maker. Raise a limitation-of-access document for generator visual inspections and a safety document or sanction for test for functional tests, with the generator isolated from all controls and distribution connections during functional tests.