NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems
Chapter 7: Installation and environmental considerations – NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems

NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems 7.6.2.3: 7.6.2.3 System load test

After the recharge period a system load test is run on the site load, augmented by a load bank sized to the ECE rating if needed, for the full class duration, following the same steps as the initial test; unity power factor is accepted for an ac SEPSS if rated power factor results are within the maker's stated design parameters.