After installation the system is tested for output and function, and an on-site acceptance test decides final approval. For battery systems: with batteries fully charged and a load bank at rated value, normal power is cut at the supplying switches; all emergency loads, including those normally off, are included; the time until the EPS takes the load, the load voltage and current and, where relevant, frequency, waveform and transients are recorded; the test runs 15 minutes or the class time if shorter, recording load and battery voltage and current and frequency; normal power is restored and the transfer time observed; then the system recharges on normal power for 24 hours.