A test may be started by the ATS test switch or by opening a normal-side breaker, which is optional; load tests include complete cold starts; and time delays are set to at least 1 second on start (0.5 second for gas turbines), no minimum on transfer, at least 5 minutes on retransfer to normal and at least 5 minutes cooldown before shutdown.