AS/NZS 3010:2017 Electrical Installations Generating Sets 3.5-changeover: 3.5 Sets supplying safety and essential services: changeover time and grouped switchgear

Automatic changeover to the emergency supply must take no longer than safety allows for the load (classes: no-break; short break within 1 s; medium break within 30 s; long break over 30 s). Apart from alarm devices, all switchgear and controlgear for the output or remote control of a set supplying safety or essential services must be clearly identified and grouped in places only authorised people can reach.