Overcurrent devices must be selected so a fault on one circuit does not impair others; sources not meant to run in parallel must be prevented from being connected together (for example by switching or mechanical interlocks); a single emergency set may supply other loads only with precautions that keep supply to safety and essential services unaffected under all conditions, and where several sources exist, other loads may be supplied only if the remaining sources can still carry all safety and essential services when one fails, which usually means automatic load shedding.