AS/NZS 3010:2017 Electrical Installations Generating Sets 3.4: 3.4 Transformers

Transformers and substations associated with a set must be installed to AS/NZS 3000, with tanks and enclosures earthed to AS/NZS 3000; instrument transformer secondary circuits must be effectively earthed unless function prevents it, and current transformers must have provision for shorting the secondary.