Philippines Occupational Safety and Health Standards
Rules 1100 to 1240: Welding, confined spaces, explosives, materials handling, boilers, pressure vessels, internal combustion engines, machine guarding, electrical safety, elevators, piping identification, power piping – Philippines Occupational Safety and Health Standards

Philippines Occupational Safety and Health Standards R1230: Rule 1230 Identification of piping systems: contents of industrial and power plant piping identified primarily by stencilled or lettered legends, supplemented by colour or colour bands at frequent intervals, near valves, changes of direction and wall and floor penetrations, with visibility, legend location and letter size rules and the PSME Code adopted

What does R1230 require?

In industrial and power plants the contents of piping systems (pipes, fittings, valves and coverings, excluding buried pipe and supports) are positively identified primarily by stencilled or lettered legends naming the content in full or abbreviated form per the Rule's table, with supplementary legends or colour for hazard or use. Colour or coloured bands supplementing the legends are applied at frequent intervals on straight runs, close to all valves, adjacent to every change of direction and at wall and floor penetrations, by paint, decals or bands conforming to the standard. Legends on overhead pipe above the operator's line of vision are placed below the horizontal centre line, legends may be concentrated at junctions and distribution points where appropriate, letters follow the type and size rules of Rule 1230.07, and the PSME Code chapter on identification is adopted for uniformity in emergencies.

Maintained by Gerard Blokdyk

Other controls in Rules 1100 to 1240: Welding, confined spaces, explosives, materials handling, boilers, pressure vessels, internal combustion engines, machine guarding, electrical safety, elevators, piping identification, power piping – Philippines Occupational Safety and Health Standards

Query this from an agent

The graph holds this control, the 0 it maps to, and the evidence behind each claim, over MCP and REST.