NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition) 17.92: Reduced test frequency only where parallel operation with the PES exists

Where the strategy and DNO arrangements let standby generators parallel with the PES, the essential systems proving test may be done less often; parallel running to offset maximum demand can supplement routine testing, allowing six-monthly frequencies.