An HV switchgear maintenance programme should be set from makers' recommendations and HSG230 and agreed with the Authorising Engineer (HV), with Authorised Persons (HV) familiar with it and HTM 06-03. Planning should minimise effects on resilience; standby generation can support isolation. A regular operational switching routine should keep function and staff competence. An HV grading and loading study should follow any network change, and the Group should consider a review within five years. Secondary injection tests should be at regular intervals set by plant history, experience and maker guidance (not staffing), with a maximum interval decided. Protection should be proof-checked before breakers return from long outages, and HV work needs a permission for disconnection document and permit-to-work.