NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems
Chapter 8: Routine maintenance and operational testing – NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems

NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems 8.4.3: 8.4.3 Load testing and ohmic trending

Each load test records output voltage, battery voltage and test duration at start and end for every battery set. Where ohmic measurement monitors lead-acid batteries, results are kept and compared with the baseline, and a deviation outside the acceptable range triggers a full-duration load test, using a load bank sized to the ECE rating in place of the actual load.