A control panel is required with automatic remote start, a run-off-automatic switch, the shutdowns, alarms and controls of 5.6.5.4 and, for Level 1, load shed controls. The automatic control and safety panel provides the full cranking cycle; shuts down and locks out on fail to start, overspeed, low oil pressure, high engine temperature, remote stop and other maker conditions; gives battery-powered individual visual alarms with common local and remote audible contacts and a lamp test (Table 5.6.5.4 lists each indication for Level 1 and Level 2); shuts down when the start signal is removed; carries the ac instruments; and, where one EPS serves Level 1 and Level 2 loads, sheds Level 2 loads and raises an overload alarm.