NFPA 110-2025 Standard for Emergency and Standby Power Systems
Chapter 5: Emergency power supply: energy sources, converters and accessories – NFPA 110-2025 Standard for Emergency and Standby Power Systems

NFPA 110-2025 Standard for Emergency and Standby Power Systems 5.6.1-5.6.2: 5.6.1 and 5.6.2 Prime mover compliance and derating

Prime movers and accessories must comply with NFPA 37 unless this standard says otherwise, and the engine maker's derating factors (elevation, ambient heat, the fuel's heating value, power drawn by accessories, site conditions) are applied in judging whether brake power covers the connected load.

Maintained by Gerard Blokdyk

What else in your programme already covers this

This control maps to 1 controls across 1 other frameworks. If you already hold one of them, the evidence you collected for it is the starting point here rather than new work.

  • 2.1.3 2.1.3 Selection of generating set rating from load characteristics

Every mapping shown was judged rather than inferred from wording similarity, and the ones that failed review are published too. See the coverage reports and what was rejected.