AS/NZS 3010:2017 Electrical Installations Generating Sets 2.1.3: 2.1.3 Selection of generating set rating from load characteristics

The minimum rating and alternator type depend on the connected load and the voltage control system: motor loads (inertia, starter type, how many start together, and the voltage dip during starting, which can drop out starter contactors), non-linear loads such as UPS, variable speed drives and rectifiers, load power factor (which should not be leading while on generator, so power-factor correction may need to be switched out), and regenerative loads, which a set cannot absorb, so other loads must take that energy. The maker's or supplier's recommendation should be sought, or their sizing software used.