AS/NZS 3000:2018 Electrical Installations (Wiring Rules)
Section 2: General arrangement, control and protection – AS/NZS 3000:2018 Electrical Installations (Wiring Rules)

AS/NZS 3000:2018 Electrical Installations (Wiring Rules) 2.10.3-2.10.7: 2.10.3 to 2.10.7 Switchboard construction, bars, identification, wiring and fire protection

Switchboards withstand service stresses and environment; they must comply with AS/NZS 3439 or 61439 where connected load exceeds 125 A per phase or the prospective fault current at its incoming side is over 10 kA. Circuit-breakers in a row open in one direction unless off is obvious; fuses and breakers are grouped and not mounted behind panels (with limited exceptions); bars terminate conductors securely with terminals identifying each circuit's active and neutral; looped neutrals stay continuous if a device is removed; equipment is identified; and fire-protective measures apply to switchboards serving safety services and in egress paths.

Maintained by Gerard Blokdyk