NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)
Chapter 17: Maintenance and operational management – NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)

NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition) 17.51-17.62: Transformer inspection, annual fluid sampling and earth continuity

Transformers should have a non-intrusive visual inspection at least yearly (leaks, fluid level, enclosure tidiness, cable boxes, ventilation, weeds cleared from external enclosures) under a limitation-of-access document. Breathers should be inspected and desiccant replaced on colour change; insulators cleaned, tanks painted and temperature gauges and alarms checked; air-cooled units inspected annually for dust and cleaned under permit. Fluid-filled transformers should be sampled annually to track condition and trends. Earth protective conductor continuity should be measured; thermal imaging may help.

Maintained by Gerard Blokdyk

Other controls in Chapter 17: Maintenance and operational management – NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)