NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)
Chapters 12 to 14: Electromagnetic compatibility, earthing, containment and cables – NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)

NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition) 13.15-13.32: Supplementary bonding and equipotential bonding busbar in Group 1 and 2 locations

Group 1 and Group 2 Medical Locations need supplementary equipotential bonding and an equipotential bonding busbar (EBB) under BS 7671 Section 710 to hold touch voltages under fault to no more than 25 V AC or 60 V DC. The EBB should be sized for the highest expected fault current (imaging), enclosed against tampering, located in or near the location with accessible, labelled, individually removable connections (not push-fit), and bonding conductors sized by calculation; Medical IT bonding should follow BS 7671. Where high protective conductor current is expected, earth monitoring may help maintain confidence in protective conductor continuity.

Maintained by Gerard Blokdyk

Other controls in Chapters 12 to 14: Electromagnetic compatibility, earthing, containment and cables – NHS England HTM 06-01 Electrical Services Supply and Distribution (2017 Edition)