At the service entrance equipment a sign tells responders what kinds of standby source are on site and where they are (individual unit equipment excepted), and where taking out a grounding or bonding link in the normal supply equipment would cut the alternate source off from the grounding electrode, a warning sign is fitted at the normal source equipment.