The emergency source must carry the total load for the duration set by the design and never less than 2 hours, except batteries and UPS for emergency illumination and unit equipment. Generators need on-site fuel for at least 2 hours; fuel transfer pumps are fed from the emergency system; sources may not rely solely on public gas or municipal water (unless the AHJ approves a low simultaneous failure risk, which also removes the on-site fuel rule); batteries and UPS for emergency lighting hold the load for at least 90 minutes without voltage falling below 87.5 percent, no automotive batteries, with automatic charging; and dual fuel systems change fuel automatically.