NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems
Chapter 6: Transfer switches and protection – NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems

NFPA 111-2025 Standard on Stored Electrical Energy Emergency and Standby Power Systems 6.2.4.4-6.2.4.6: 6.2.4.4 to 6.2.4.6 Manual operation, retransfer delay and test switch

Instructions and equipment must allow manual nonelectric transfer or bypass if the ATS fails; an adjustable delay with automatic bypass holds off retransfer to the preferred source and that delay is skipped automatically if the ECE or EPS fails; and each ATS has a test switch that simulates preferred-source failure, after which the ATS must do its job.